3 Cups Insulation Oil BDV Tester 80/100kV
HV Hipot Electric Co., Ltd.- Type:Oil BDV Tester
- Accuracy Grade:1
- Load Way:Electronic Load
- Loading Method:Dynamic Load
- Display:Digital
- Control:Computer Control
Base Info
- Model NO.:GDOT-3C
- Weight:38kg
- Power Source:AC220V
- Oil Cylinder Position:Top
- Output voltage:0-80kV optional
- Power distortion rate:<1%
- Voltage increasing speed:2.0kV,s, 2.5kV,s, 3.0kV,s, 3.5kV,s optional ,Error
- Voltage accuracy:2%* reading + 2 digital
- Output Capacity:1.5kVA
- Test Accuracy:±3%
- Transport Package:Standard Export Wooden Box
- Specification:670mm*420mm*410mm
- Trademark:HV Hipot
- Origin:Wuhan, China
- HS Code:9031809090
- Production Capacity:5000sets,Year
Description
Basic Info.
Model NO. GDOT-3C Weight 38kg Power Source AC220V Oil Cylinder Position Top Output voltage 0-80kV optional Power distortion rate <1% Voltage increasing speed 2.0kV/s, 2.5kV/s, 3.0kV/s, 3.5kV/s optional ,Error Voltage accuracy 2%* reading + 2 digital Output Capacity 1.5kVA Test Accuracy ±3% Transport Package Standard Export Wooden Box Specification 670mm*420mm*410mm Trademark HV Hipot Origin Wuhan, China HS Code 9031809090 Production Capacity 5000sets/YearProduct Description
GDOT-3C 80kV 3 Cups Insulation Oil Breakdown Voltage (BDV)TesterGDOT-3C 80kV 3 Cups Insulation Oil Breakdown Voltage Tester is fully digital industrial instrument with microcomputer control. It has the features of high accuracy and strong anti-interference ability.
Features
- LCD screen display.
- Single-chip control, easy to control.
- Wide range watchdog circuit to avoid system halted.
- Unique HV sampling design to make the test data entering into A/D converter directly, to avoid error caused by analog circuit, which will make measurement more accurate.
- Automatic completing all test procedures.
- 1-6 times breakdown voltage value and times will be saved automatically. It will print test results.
- With over-voltage, over-current and short circuit protection.
- Portable design, easy to move.
Specifications
Output voltage | 0-80kV optional |
Power distortion rate | <1% |
Voltage increasing speed | 2.0kV/s, 2.5kV/s, 3.0kV/s, 3.5kV/s optional ,Error 0.2kV/s. |
Voltage accuracy | 2%* reading + 2 digital |
Display | Large LCD screen |
Electrode gap | standard 2.5mm |
Test time | 6 times(1-6 times optional) |
Static time | 5 min (1-9 min optional) |
Booster Capacity | 1.5kVA |
Power input | AC220V± 10%, 50Hz±1Hz |
Power | 200W |
Working temperature | 0-40ºC |
Humidity | <85%RH |
Dimension | 670mm*420mm*410mm |
Weight | 38kg |