GD-4138H Moveable Cable Fault Locating System Underground Cable Fault Finder
HV Hipot Electric Co., Ltd.- Connectors:USB
- Test Mode:Point Test
- Test Region:Forming Cable
- Cable Type:Shielded
- Power:Electricity
- Customized:Customized
Base Info
- Model NO.:GD-4138H
- Color:Yellow
- power supply:AC220V,50Hz
- warranty:1 year
- Transport Package:Wooden Box
- Specification:ISO, SGS
- Trademark:HV Hipot
- Origin:Wuhan, China
- HS Code:9030899090
- Production Capacity:5000sets,Year
Description
Working mode
low voltage pulse, pulse current, multiple pulse.
Signal gain adjustment range
70dB.
Low-voltage pulse emission voltage
30V.
The highest resolution
0.4m.
Maximum sampling frequency
200MHz real-time sampling.
Maximum ranging range
100km.
Distance measurement blind zone
2m.
Communication interface
USB.
Power
Polymer lithium-ion battery pack, nominal voltage 7.4V.
Button
Adopt Danish imported button, the reliability is not less than 10 million times.
Battery life
Use a fully charged polymer lithium-ion battery for more than 5 hours of continuous use (as the battery ages, the continuous use time will be shortened accordingly).
Charger
Input AC220V, 50Hz, charging current 2A, charging time 8 hours.
Volume
274 * 218 * 81mm
Weight
3.5kg
Conditions of Use
Temperature
-10ºC~ +40ºC;
Humidity
5% to 90% RH (25 ºC);
Altitude
h<4500m
II. GD-4132 Power Cable Fault Locator
GD-4132 cable tracing and fault locator is used with the GD-2131H integrated DC high voltage power supply unit to provide an advanced acoustic and magnetic waveform display acoustic and magnetic synchronization method to precisely determine the fault point.
Features
a. Acoustic and magnetic synchronous receiving, strong anti-interference ability.
b. Acoustic and magnetic signal waveform display, signal and noise are easy to distinguish.
c. The cursor measures the acoustic and magnetic delay to accurately determine the distance of the fault point.
d. Path detection can be performed at the same time as the fixed point according to the initial polarity of the magnetic field waveform.
e. High performance anti-noise headphones.
f. Large-screen LCD display, friendly interface and easy to use.
g. Built-in high-capacity lithium-ion battery power supply with fast charger.
h. Power management: Open different power paths according to different functions to minimize power consumption; if there is no operation for 15 minutes, the instrument will automatically shut down; when the battery is under voltage, it will automatically shut down to protect the battery.
i. High degree of protection, small and portable.
Specifications
Acoustic and magnetic synchronous fixed point function
Sound signal passband
center frequency 400Hz, bandwidth 200Hz
Signal gain
80dB
Fixed point accuracy
0.1m.
Power supply
Battery
Built-in lithium-ion battery pack, nominal voltage 7.4V, capacity 3000mAH
Power consumption
300mA, continuous use time > 9 hours
Charger
Input AC220V±10%, 50Hz; nominal output 8.4V, DC1A
Charging time
<4 hours
Display mode
320×240 dot matrix large screen LCD
Volume
270mm * 150mm * 210mm
Weight
1.5kg
Conditions of use
Temperature
-10 ° C -40 ° C
Humidity
5-90% RH
Altitude
<4500 m
III. GD-4133S Cable Test Multiple Pulse Coupling Device
GD-4133S cable test multiple pulse coupling device is used together with GD-4133 cable multiple pulse fault range finder and high voltage signal generator to detect high resistance leakage fault, flashover fault, low resistance, ground and open circuit failure of various power cables.. The GD-4133S provides a pulse signal coupling path for the GD-4133 cable multiple pulse fault finder, and at the same time achieves electrical isolation from high voltage equipment. It adopts the most advanced "multiple pulse method" technology in the world to make the judgment of cable fault waveforms simple and convenient.
Features
1. Adopted the most advanced "multiple pulse method" technology and pulse balance technology, which further highlights the reflection waveform of the fault point, and the test waveform identification is easier.
2. It has safe high-voltage protection measures to achieve electrical isolation between the measuring circuit and the high-voltage impact power supply, ensuring the safety of the range finder in the impact voltage environment without damage or crash.
3. Simple wiring and can be used with other high voltage equipment.
4. No high pressure exposed, safe and reliable.
Specifications
Test pulse voltage
300V (P-P)
Allow input impulse voltage
less than 35kV
Allow input of impact energy
less than 2000J
Power supply
AC 220V, 50Hz
Dimesion
560mm × 230mm × 220mm
Weight
7kg
IV. GD-2131H Integrated DC High Voltage Power Supply
GD-2131H integrated DC high voltage power supply unit is an integral part of the cable fault detection system and is used to detect the auxiliary high voltage power supply when using the impact flashover method to detect high resistance faults.
Features
1. Strong burning ability, the maximum burning power of 1000W, can burn through the breakdown point in a short time, reducing the breakdown point resistance.
2. In conjunction with the GD-4133 Cable Fault Tester, it has the following two positioning methods:
a. Low-voltage pulse method: GD-4133 can be used alone to locate the open circuit and low-resistance ground fault of the cable, and measure the cable length or verify the cable wave speed.
b. High-voltage flashover method: The pulse current waveform discharged by the fault point is sampled by the discharge ball gap, and the distance of the fault point can be located.
3. Generates a fixed frequency pulse that, in conjunction with the GD-4132 Cable Fault Locator, has the following features:
a. Use the audio method to complete the precise determination of the general high-resistance and flashover fault points.
b. Find the location (path) of the cable and identify the specific cable.
c. For metallic breakdown (dead ground), use magnetic field measurement to determine the point.
4. DC withstand voltage test is available.
5. Optional 30m or 50m cable reel for user convenience.
Technical indicators
Output voltage
DC 0-32kV adjustable
Direct flash voltage
32kV
Direct flash current
32mA
Maximum pulse current
500mA
Maximum energy storage
2048J, 4uF
Rated power
2000VA
Discharge mode
DC high voltage, single time, cycle.
Periodic discharge frequency
3-6 seconds.
Power supply
AC 220V, 50Hz
Insulation class
Class A
Ambient temperature and humidity
0~40oC <75%RH
Altitude
<1000m
Volume
460mm × 380mm × 380mm
Weight
75kg