Test Instrument

Thermal Protection (Radiation) Performance Testing Equipment

Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.
  • Item Name:Thermal Protection (Radiation) Performance Tester
  • Standard:En 366; ISO 6942
  • Application:Fire Testing Equipment Flammability Analyzer
  • Manual:Provide
  • Warranty:12 Months
  • Thermocouple:Copper, Constantan (T); Diameter: 0.25mm

Base Info

  • Model NO.:GD8965
  • Calorimeter:Copper Specifications: Thickness 1.6 mm; Purity:
  • Heat Flux Density:10kw,M2 ~ 80 Kw,M2 Adjustable
  • Operating Platform:Windows Operating Systems;
  • Power:AC 220V 50Hz
  • Outline Dimension:W1510×d650×h1220mm
  • Weight:About 200kg
  • Transport Package:Standard Wooden Case
  • Trademark:GOLD
  • Origin:Chongqing China(Mainland)
  • HS Code:9031809090
  • Production Capacity:500 Sets, Year

Description

Basic Info.

Model NO. GD8965 Calorimeter Copper Specifications: Thickness 1.6 mm; Purity: Heat Flux Density 10kw/M2 ~ 80 Kw/M2 Adjustable Operating Platform Windows Operating Systems; Power AC 220V 50Hz Outline Dimension W1510×d650×h1220mm Weight About 200kg Transport Package Standard Wooden Case Trademark GOLD Origin Chongqing China(Mainland) HS Code 9031809090 Production Capacity 500 Sets/ Year

Product Description

Introduction: 

Thermal protection (radiation) performance testing in accordance with ISO6942 and EN366 standards of design and manufacturing. This tester fully compliant to test requirements and received US and European customers' exception; The device has a user-friendly, intuitive, Windows-based application that provides a complete thermal control, fault detection and data recording. RPP system configuration and burn prediction also included in the Therm DAC.The user-defined test allows the operator to define non-standard test conditions and custom tolerances. You can view multiple graphs display with a zoom feature to view specific conditions in details. Real-time statistics can be applied to the test data within any user-selected time range.

 

This tester used for performance evaluation against heat and flame protective clothing when faced with short flame thermal motion. Imposed a certain calorie density (80KW/m ² ± 5%) of heat, under the specimens that composed of protective clothing. When measuring the growth rate of heat through overtime (time: seconds, temperature: ºC) by heat meter that installed on  test sample, to determine the insulation properties of sample materials. This apparatus is applied to measuring the fabric of single-layer or multi-layer under high-temperature thermal radiation properties, can also be used for other fire-retardant insulation of plates.

 

Standard:

EN 366, ISO 6942
 

Feature: 

1, The tester consists of a radiation device, the specimen clamping device and control system;

2, Stainless steel frame structure, appearance, corrosion resistance, easy to clean;

3, Specimen size: 230mm x 80mm;

4, Radiation source is made up of 5 infrared quartz lamp, power 500W, and provide at least 80kW/m2 radiant heat;

5, Standard copper heat flow meter, heat measuring range 0~100kw/m2;

6, A cooling device (cooling water inlet);

7, Intelligent water circulation control system;

8, The water temperature alarm function; ensure the safe operation and test stability;

9, Computer control system; to achieve more intelligent test and easy to operate;

10, Timer accuracy is 1s;

11, Constantan thermocouple: measurement Accuracy 0.1 ºC, meet the design requirements of ISO 6942

12, Metal protection shutters, with water cooling device;

13, Computer records and displays real-time continuous temperature curve;

14, Automatic operation mode, test time can be set freely.

15, According to ISO 6942-2002 (EN366) standards, there are two methods to test the thermal protection;

16, The first method (A method) is a specimen to withstand a certain amount of heat radiation, recording changes in appearance in order to reproduce the material the inclement conditions.

17, The second method (B method) is a calorimeter inside a specimen back, when heat conduction from samples back, recording temperature trends over time, in order to determine the level of thermal radiation transfer.

Specification:

Model

ISO6942

Thermocouple

Copper, Constantan (T); diameter: 0.25mm

Calorimeter

Copper Specifications: Thickness 1.6 mm; purity: 99.95%

Press Release Plate

Specification:149×149×6t mm(center:φ90mm hole)weight:264±13g

Heat flux density

10kW/m2 ~ 80 kW/m2 adjustable;

Thermal radiation temperature control

Room temperature ~ 1200ºC ± 5ºC (display accuracy of 1ºC; having PID smart regulation Controller

Thermal radiation temperature sensor

Thermocouple (0 ~ 100ºC)

Circulating pump

HQB-3900/100W/220V/50Hz

Operating platform

Windows operating systems;

Flame shield plate

Operation: manual/automatic front pulled way;

Material: heat-resistant inorganic-based thermal materials

Power

AC 220V 50Hz

Outline dimension

W1510×D650×H1220mm

Weight

About 200kg