Test Instrument

0~32kV Underground Cable Fault Locator/Cable Fault Test System

HV Hipot Electric Co., Ltd.
  • Connectors:USB
  • Usage:Cable Testing
  • Test Region:LCD Screen
  • Cable Type:HV Cable, Communication Cable
  • Power:Electricity
  • Certification:ISO

Base Info

  • Model NO.:GD-4136H
  • Customized:Non-Customized
  • Color:Yellow
  • Power Supply:AC 220V; 50Hz
  • Output voltage:DC 0-32kV (adjustable)
  • Rated power:2kVA
  • Max.energy:2048J, 4UF
  • DC flashover voltage:32kV
  • DC flashover current:63mA
  • Max.impulse current:500mA
  • Discharging method:DC HV, one time, cycle
  • Cycle discharging time:3-6 seconds
  • Transport Package:Wooden Case
  • Specification:ISO, SGS
  • Trademark:HV Hipot
  • Origin:China
  • HS Code:9030332000
  • Production Capacity:1000PCS,Year

Description

Locating functiona. Acoustic signal transmission band: center frequency 400Hz, bandwidth 200Hz
b. Signal gain: 80dB
c. Locating accuracy: 0.1m
Power Supplya.Built-in Li-battery, nominal voltage 7.4V, capacity 3000mAH.
b.Power consumption: 300mA, continuous working time 9hours.
c.Charger: input AC220V±10%, 50Hz. Nominal output 8.4V, DC 1A
d.Charging time: 4hours
Dimension270mm*150mm*210mmWeight1.5kg.Use conditionTemperature -10ºC--40ºC, humidity 5-90%RH, altitude <4500m

 
GD-4133 Cable Fault Detector

GD-4133 Cable Fault Locator is used to measure distance between cable faults. It's easy to operate and with friendly interface.
It can be used alone under the low voltage pulse mode. Under the mode of pulse current, it needs to work with GD-2131 high voltage generator. Under the multiple pulse mode, GD-4133S coupler should be worked together. After distance locating, GD-4132 fault locator should be used for fault pinpointing. These products can be combined into a set of high performance and innovative cable fault testing system.
 
Features

1. 7inch LCD screen, friendly interface.
2. Multiple distance locating method:
a. Low voltage pulse method: it is suitable for the locating of the low resistance fault, short circuit fault, open circuit fault. It also can be used in the measurement of the cable length, the intermediate joints, T joints, and cable termination joint. This method also can be used to correct the wave velocity.
b. Pulse current method: It is suitable for distance measurement of the high resistance fault, breakdown fault. Using the current coupler to collect signals from the earth wire, it makes the user far away from the high voltage. This method is safe and reliable. 
c. Multiple pulse: the advanced way to measure distance. The waveform is easy to identify and the accuracy is high.
3. 200MHz real-time sampling. Max. 0.4m measurement resolution. It has small dead zone and is special for the short cable and near fault cable.
4. Touch screen and press key operation
5. PIP copy(pic. temporary storage)
6. There will be a main window and three temporary storage windows could check three waveforms together.
7. Built-in operating system
8. Special software management for software upgrade, backup and restore.
Scale function
A starting point,10 contacts, one cable fault and one full length could be setting. 
Display scale and testing waveform together
Waveform storage and communication with computer.
Internal storage of waveforms.
With USB, to download or upload data
Communication with computer
Power management
Backlight weakens if no operation in 2mins and power off in 10mins if no operation. 
Built-in Polymer Lithium-ion battery. 
Working time is up to 5 hours for each use. 
Strong case, easy to carry.
 

GD-4133S Multiple Pulse Coupler

It is working together with GD-4133 Cable Fault Detector, used for detecting high impedance leak fault, flashover fault, low impedance earth and open circuit fault of power cables. GD-4133S supplied pulse coupling signal for GD-4133 and isolate it from high voltage equipment.
 
Features

Using the most advanced technology of multiple pulse and pulse balance. The reflected waveform is more easy to identify.
With safety HV protection, the measuring circuit and high voltage impulse power is electrically isolated.
Easy wiring, safe and reliable.

Specifications

 Pulse voltage300V(P-P)Allowable input impulse voltage<35kVAllowable input impulse energy<2000JPower input220V AC, 50HzDimension560*230*220mmWeight7kg.
0~32kV Underground Cable Fault Locator/Cable Fault Test System
0~32kV Underground Cable Fault Locator/Cable Fault Test System