Test Instrument

Gdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester

Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.
  • Internal Hv:0.5~10kv
  • Input Current Range:10μa~1A
  • Test Standards:IEC 60247,Iiec 61620,ASTM D924
  • Condition of Use:-5°c~40°c, Rh<80%
  • Frequency of Self-Excited Power:45Hz ,55Hz
  • Maximum Current of Self-Excited Power:15A

Base Info

  • Model NO.:GDGS
  • Maximum Output Capacity:200mA
  • Power Supply:AC220V±10 % 50Hz,60Hz
  • Warranty:12 Months
  • Product Name:Transformer Tan Delta Tester
  • Transport Package:Standard Wooden Case
  • Specification:23kg
  • Trademark:GOLD
  • Origin:Chongqing, China (Mainland)
  • HS Code:9031809090
  • Production Capacity:50PCS,Month

Description

GDGS Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester

1

Use conditions

-15ºC∽40ºC

RH<80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%

Allowable generator

4

High output

0.5KV∽10KV

Every 0.1kV

Precision

2%

Maximum current  

200mA

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF

 

10KV

Cx < 60  nF

 

 5KV

Cx < 150 nF

 

 1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350(L)×270(W)×270(H)

11

Memory size

The 200 group supports U disk data storage

12

Weight

28 Kg


Product Details :

Gdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester

Gdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester

Success Case:
Gdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor TesterGdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester
Gdgs Power Transformer Dielectric Loss Capacitance and Tan Delta Tester Power Factor Tester
Customers Visit: