Primary Current Injection Test Set GDSL-82-5000
HV Hipot Electric Co., Ltd.- Model number:GDSL-82-5000
- Output current:0-5000A AC
- Output Voltage:6V
- Capacity:30kVA
- Input voltage:AC380V, Single phase, 50Hz
- Input current:78.9A
Base Info
- Model NO.:GDSL-82-5000
- Delivery time:25-30 days
- Transport Package:Wooden Case
- Specification:ISO, SGS
- Trademark:HV Hipot
- Origin:Wuhan China
- HS Code:9030899090
Description
Basic Info.
Model NO. GDSL-82-5000 Delivery time 25-30 days Transport Package Wooden Case Specification ISO, SGS Trademark HV Hipot Origin Wuhan China HS Code 9030899090Product Description
I. General Information
GDSL-82-5000 Primary Current Injection Test Set is the ideal equipment for testing high-current device in the power and electric industry, used in power plants, distribution stations, electrical manufacturing and research institutes, with the features of small size, light weight, easy use and maintenance.
II. Features
1. Manual control.
2. Equipment with wheels, easy to move.
3. Customized current output, current output is adjustable.
4. With timer to timing the action time of circuit breaker.(customized)
5. Suitable for all kinds of circuit breaks, current relays.
III. Specifications
Output current | 0-5000A AC |
Output voltage | 6V |
Capacity | 30kVA |
Input voltage | AC380V, Single phase, 50Hz. |
Input current | 78.9A |
Operating time | 1 min ON, 5 mins OFF |
Time range | 0.001-99999ms |
Ambient temperature | -20 ºC to 50 ºC |
Current accuracy | ≤ 1.0% (F.S) |